Feature
| Battery Input Data |
||||||
| Battery Type | Lithium-ion | |||||
| Battery Voltage Range (V) | 160~800V | |||||
| Max. Charging Current (A) | 50+50 | |||||
| Max. Discharging Current (A) | 50+50 | |||||
| Number of Battery Input | 2 | |||||
| Charging Strategy for Li-Ion Battery | Self-adaption to BMS | |||||
| PV String Input Data |
|||||
| Max. DC Input Power (W) | 38870 | 39000 | 45500 | 52000 | 65000 |
| Rated PV Input Voltage (V) | 1000 | ||||
| Start-up Voltage (V) | 180 | ||||
| MPPT Range (V) | 150-850 | ||||
| Full Load DC Voltage Range (V) | 360-850 | 360-850 | 420-850 | 360-850 | 450-850 |
| Rated DC Input Voltage(V) | 600 | ||||
| PV Input Current (A) | 36+36+36 | 36+36+36+36 | |||
| Max. PV ISC (A) | 55+55+55 | 55+55+55+55 | |||
| Number of MPPT / Strings per MPPT | 3/2+2+2 | 3/2+2+2 | 3/2+2+2 | 4/2+2+2+2 | 4/2+2+2+2 |
| AC Output Data | |||||
| Rated AC Output and UPS Power (W) | 29900 | 30000 | 35000 | 40000 | 50000 |
| Max. AC Output Power (W) | 29900 | 33000 | 38500 | 44000 | 55000 |
| Peak Power (off grid) | 1.5 times of rated power, 10 S | ||||
| AC Output Rated Current (A) | 45.4/43.4 | 45.5/43.5 | 53.1/50.8 | 60.7/58 | 75.8/72.5 |
| Max. AC Current (A) | 45.4/43.4 | 50/47.8 | 58.4/55.8 | 66.7/63.8 | 83.4/79.7 |
| Max. Continuous AC Passthrough (A) | 60 | 60 | 60 | 70 | 83.3 |
| Generator Input/Smart Load/AC Couple Current(A) | 45.4/200/45.4 | 45.5/200/45.5 | 53.1/200/53.1 | 60.7/200/60.7 | 75.8/200/75.8 |
| Max.Continuous AC Passthrough(A) | 200 | ||||
| Output Frequency and Voltage | 50/60Hz;3L/N/PE 220/380,230/400Vac | ||||
| Grid Type | Three Phase | ||||
| Total Harmonic Current Distortion(THDi) | <3%(of nominal power) | ||||
| DC Current Injection | <0.5% In | ||||
| Efficiency | |
| Max. Efficiency | 97.60% |
| Euro Efficiency | 97.00% |
| MPPT Efficiency | 99.90% |
| Protection | |
| PV Input Lightning Protection | Integrated |
| Anti-islanding Protection | Integrated |
| PV String Input Reverse Polarity Protection | Integrated |
| Insulation Resistor Detection | Integrated |
| Residual Current Monitoring Unit | Integrated |
| Output Over Current Protection | Integrated |
| Output Shorted Protection | Integrated |
| Output Over Voltage Protection | Integrated |
| Surge protection | DC Type II / AC Type II |
| Certifications and Standards | |
| Grid Regulation | IEC 61727,IEC 62116,CEI 0-21,EN 50549,NRS 097,RD 140,UNE 217002,OVE-Richtlinie R25,G99,VDE-AR-N 4105 |
| Safety EMC / Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |
| General Data | |
| Operating Temperature Range (℃) | -40~60℃, >45℃ Derating |
| Cooling | Smart cooling |
| Noise (dB) | <65 dB |
| Communication with BMS | CAN |
| Weight (kg) | 80 |
| Size (mm) | 527W×894H×294D |
| Protection Degree | IP65 |
| Installation Style | Wall-mounted |
| Warranty | 5 years |